1 the influence of ambient temperature on the compressive deformation of the vibration isolator should be considered;
2 calculate the amount of compression deformation according to the limit of the amount of compression provided by the manufacturer 1/3-1/2;
3 the ratio of the operating frequency of the equipment and the vertical direction of the rubber vibration isolator should be greater than or equal to 2.5;
4 the load of the rubber vibration isolator should not be more than the allowable working load;
5 elastic vibration isolation pad with a certain thickness between the base and the rubber vibration isolator.